摘要 | The air-source heat pump with an economized vapor injection technique has the distinct advantages of performance and stability for space heating and hot water supply in cold area. However, it is unreasonable to evaluate and predict the thermal performance by the nominal working conditions in different areas and environmental conditions. The experimental set up of economized vapor injection air-source heat pump (EVI-ASHP) system was established in cold region of China. The experimental results showed that the air-source heat pump with the EVI technique could improve thermal performance 4-6% than that without EVI. The relationship of COP and condenser inlet and ambient temperature difference was linearly dependent in the same environmental relative humidity. In order to obtain the empirical equations of COP, the linear and negative exponential corrections of the temperature difference of ambient dry-bulb and wet bulb were used when the electromagnetic valve is on or off, respectively. The monthly and hourly thermal performance of four cities in cold and severe cold region in China was compared and analyzed in the climatic condition of the typical meteorological year. (C) 2016 Published by Elsevier Ltd. |
关键词 | Air source heat pump COP Economized vapor injection Thermal performance prediction Cold climate |
DOI | 10.1016/j.seta.2016.10.008 |
收录类别 | SCI ; SCIE |
语种 | 英语 |
WOS研究方向 | Science & Technology - Other Topics ; Energy & Fuels |
WOS类目 | Green & Sustainable Science & Technology ; Energy & Fuels |
WOS记录号 | WOS:000388029300012 |
出版者 | ELSEVIER SCIENCE BV |
EI入藏号 | 20164703044059 |
EI主题词 | Air source heat pumps |
EI分类号 | 446.1 Water Supply Systems - 616.1 Heat Exchange Equipment and Components - 618.2 Pumps |
引用统计 | |
文献类型 | 期刊论文 |
条目标识符 | https://ir.lut.edu.cn/handle/2XXMBERH/33518 |
专题 | 能源与动力工程学院 机电工程学院 |
通讯作者 | Li, Jinping |
作者单位 | 1.Lanzhou Univ Technol, Western China Energy & Environm Res Ctr, Lanzhou 730050, Peoples R China; 2.Lanzhou Univ Technol, Sch Energy & Power Engn, Lanzhou 730050, Peoples R China; 3.Key Lab Complementary Energy Syst Biomass & Solar, Lanzhou 730050, Peoples R China |
第一作者单位 | 能源与动力工程学院 |
通讯作者单位 | 能源与动力工程学院 |
第一作者的第一单位 | 能源与动力工程学院 |
推荐引用方式 GB/T 7714 | Zhang, Dong,Li, Jinping,Nan, Junhu,et al. Thermal performance prediction and analysis on the economized vapor injection air-source heat pump in cold climate region of China[J]. SUSTAINABLE ENERGY TECHNOLOGIES AND ASSESSMENTS,2016,18:127-133. |
APA | Zhang, Dong,Li, Jinping,Nan, Junhu,&Wang, Linjun.(2016).Thermal performance prediction and analysis on the economized vapor injection air-source heat pump in cold climate region of China.SUSTAINABLE ENERGY TECHNOLOGIES AND ASSESSMENTS,18,127-133. |
MLA | Zhang, Dong,et al."Thermal performance prediction and analysis on the economized vapor injection air-source heat pump in cold climate region of China".SUSTAINABLE ENERGY TECHNOLOGIES AND ASSESSMENTS 18(2016):127-133. |
条目包含的文件 | 下载所有文件 | |||||
文件名称/大小 | 文献类型 | 版本类型 | 开放类型 | 使用许可 | ||
Zhang-2016-Thermal p(1797KB) | 期刊论文 | 出版稿 | 开放获取 | CC BY-NC-SA | 浏览 下载 |
除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。
修改评论