Thermal performance evaluation and prediction of enhanced vapor injection air source heat pump | |
Zhang, Dong![]() ![]() ![]() ![]() | |
2014-12-01 | |
发表期刊 | Huagong Xuebao/CIESC Journal
![]() |
ISSN | 04381157 |
卷号 | 65期号:12页码:5004-5009 |
摘要 | The enhanced vapor injection air source heat pump (EVI-ASHP) has better thermal performance at a low temperature, which has received much attention to supply hot water in cold region in recent years due to the growing space heating load and concern for environmental degradation. Environmental temperature is often below -5 in winter in cold region of China, and changes greatly throughout the year. Thus coefficient of performance (COP) under nominal working conditions (dry-bulb temperature of 7) is difficult to accurately reflect the actual energy-saving effect of the system. So, a set-up of EVI-ASHP system was built in Lanzhou, and thermal performance at different environmental temperatures and humidities was determined. COP of the EVI-ASHP system could reach above 6.5 when electromagnetic valve for vapor injection was off, and linear change of COP was observed. At a low temperature, when electromagnetic valve was on, COP was about 2.0. The fitting equations of the experimental data were obtained and verified, with average relative error below 3% compared with the experimental data from the set-up. An effective prediction method was established for thermal performance of the EVI-ASHP system at changeable environmental temperature and humidity, supplying a theoretical guidance for the application of the system in cold climate. ©, 2014, Chemical Industry Press. All right reserved. |
关键词 | Coefficient of performance Energy conservation Forecasting Mathematical models Pumps Temperature Average relative error Dry bulb temperature Electromagnetic valves Energy-saving effect Environmental temperature Experimental validations Thermal performance evaluations Vapor injection |
DOI | 10.3969/j.issn.0438-1157.2014.12.048 |
收录类别 | EI |
语种 | 中文 |
出版者 | Chemical Industry Press |
EI入藏号 | 20150300426222 |
EI主题词 | Air source heat pumps |
EI分类号 | 525.2 Energy Conservation - 618.2 Pumps - 641.1 Thermodynamics - 641.2 Heat Transfer |
来源库 | Compendex |
分类代码 | 525.2 Energy Conservation - 618.2 Pumps - 641.1 Thermodynamics - 641.2 Heat Transfer |
引用统计 | 无
|
文献类型 | 期刊论文 |
条目标识符 | https://ir.lut.edu.cn/handle/2XXMBERH/113050 |
专题 | 新能源学院 能源与动力工程学院 机电工程学院 |
作者单位 | Western China Energy and Environment Research Center, Lanzhou University of Technology, Lanzhou ; Gansu; 730050, China |
第一作者单位 | 新能源学院 |
第一作者的第一单位 | 新能源学院 |
推荐引用方式 GB/T 7714 | Zhang, Dong,Li, Jinping,Liu, Wei,et al. Thermal performance evaluation and prediction of enhanced vapor injection air source heat pump[J]. Huagong Xuebao/CIESC Journal,2014,65(12):5004-5009. |
APA | Zhang, Dong,Li, Jinping,Liu, Wei,Nan, Junhu,&Wang, Linjun.(2014).Thermal performance evaluation and prediction of enhanced vapor injection air source heat pump.Huagong Xuebao/CIESC Journal,65(12),5004-5009. |
MLA | Zhang, Dong,et al."Thermal performance evaluation and prediction of enhanced vapor injection air source heat pump".Huagong Xuebao/CIESC Journal 65.12(2014):5004-5009. |
条目包含的文件 | 条目无相关文件。 |
除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。