Numerical investigation on the thermal-flow performance of humid air-water in the interspace outside staggered tube bundles | |
Ma, Hongqiang1,2,3; Liu, Yemin1,2; Hou, Caiqin2; Wang, Gang2; Luo, Xinmei1 | |
2021-02 | |
发表期刊 | International Journal of Heat and Mass Transfer |
ISSN | 00179310 |
卷号 | 166 |
摘要 | A new model was established to investigate the thermal-flow performance of humid air-water in the interspace outside staggered tube bundles. The formation of spray water film, heat and mass transfer process between humid air and spray water including spray water droplets and film were considered in this model. The influence of structure parameters was analyzed for thermal-flow performance of humid air-water in the interspace outside staggered tube bundles. It can be found that to increase the longitudinal and transverse distance between tube bundles can improve the heat transfer performance between spray water and wall of tube bundles, and decrease the pressure drop of humid air-water. But the mass transfer between spray water and humid air will only decrease with the transverse distance between tube bundles. Meanwhile, the relative humidity of humid air is not fully utilized at the top of staggered tube bundles when the transverse distance is more than 20 mm. Otherwise, the spray water will be lost heavily at the 19–24th rows of staggered tube bundles. The row number of staggered tube bundles should be reasonably designed in term of the transverse distance. The new correlations of heat transfer and pressure drop are also obtained in term of the simulation results. The Parker's correlation will be also recommended to design the mass transfer performance of that. © 2020 |
关键词 | Air Drops Mass transfer Pressure drop Tubes (components) Heat and mass transfer process Heat transfer and pressure drop Mass transfer performance New correlations Numerical investigations Spray water Structure parameter Thermal flows |
DOI | 10.1016/j.ijheatmasstransfer.2020.120784 |
收录类别 | EI ; SCIE |
语种 | 英语 |
WOS研究方向 | Thermodynamics ; Engineering ; Mechanics |
WOS类目 | Thermodynamics ; Engineering, Mechanical ; Mechanics |
WOS记录号 | WOS:000609976900031 |
出版者 | Elsevier Ltd |
EI入藏号 | 20205109625981 |
EI主题词 | Heat transfer performance |
EI分类号 | 619.1 Pipe, Piping and Pipelines - 641.3 Mass Transfer - 804 Chemical Products Generally |
来源库 | Compendex |
引用统计 | |
文献类型 | 期刊论文 |
条目标识符 | https://ir.lut.edu.cn/handle/2XXMBERH/147144 |
专题 | 土木工程学院 |
通讯作者 | Ma, Hongqiang; Luo, Xinmei |
作者单位 | 1.East China Jiaotong Univ, Sch Civil Engn & Architecture, Nanchang, Jiangxi, Peoples R China; 2.Lanzhou Univ Technol, Sch Civil Engn, Lanzhou, Peoples R China; 3.Sinopec Petr Engn Zhongyuan Corp, Puyang, Peoples R China |
第一作者单位 | 兰州理工大学 |
通讯作者单位 | 兰州理工大学 |
推荐引用方式 GB/T 7714 | Ma, Hongqiang,Liu, Yemin,Hou, Caiqin,et al. Numerical investigation on the thermal-flow performance of humid air-water in the interspace outside staggered tube bundles[J]. International Journal of Heat and Mass Transfer,2021,166. |
APA | Ma, Hongqiang,Liu, Yemin,Hou, Caiqin,Wang, Gang,&Luo, Xinmei.(2021).Numerical investigation on the thermal-flow performance of humid air-water in the interspace outside staggered tube bundles.International Journal of Heat and Mass Transfer,166. |
MLA | Ma, Hongqiang,et al."Numerical investigation on the thermal-flow performance of humid air-water in the interspace outside staggered tube bundles".International Journal of Heat and Mass Transfer 166(2021). |
条目包含的文件 | 条目无相关文件。 |
除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。
修改评论