The difference between vapor injection cycle with flash tank and intermediate heat exchanger for air source heat pump: An experimental and theoretical study
Qv, Dehu
2021
发表期刊Energy
ISSN03605442
卷号221期号:/
摘要

As a widely used technique, vapor injection plays an important role in air source heat pumps (ASHPs) which operate across a wide range of ambient temperatures. The one of primary solutions has been reported to be vapor injection based on flash-tank (FT) and intermediate heat exchanger (IHX) loops respectively. In this paper, vapor injection and its two typical configurations are experimentally investigated in an ASHP prototype. The results show that in the vapor-injection based ASHPs, the performance of FT based ASHPs is better than that of IHX based ones, and injected vapor improves mass flow rate and distribution of working fluid, with a hidden decreasing effect of exhaust entropy. In order to explore theoretical reasons, a whole system model is presented that quantifies performance enhancement potential of FT based and IHX based ASHPs respectively. The calculation results show increased refrigerant mass flow rate, its optimum distribution, and moderate injected vapor entropy contribute to performance improvement of vapor-injection based ASHPs. Further, we also visualize synergy between refrigerant mass flow and injected entropy from perspective of negentropy. At the negentropy level, FT based rather than IHX based loop brings higher heating capacity and efficiency, which is consistent with measurements from experimental research.

关键词Air source heat pumps Vapor-injection configurations Refrigerant mass flow and distribution Injected entropy Negentropy
学科门类工学
DOI10.1016/j.energy.2021.119796
收录类别SCI
语种英语
出版者Elsevier Ltd
EI入藏号20210509859619
EI主题词Air source heat pumps
EI分类号619.2 Tanks - 641 Heat and Mass Transfer ; Thermodynamics - 803 Chemical Agents and Basic Industrial Chemicals
引用统计
被引频次:20[WOS]   [WOS记录]     [WOS相关记录]
文献类型期刊论文
条目标识符https://ir.lut.edu.cn/handle/2XXMBERH/146975
专题土木工程学院
通讯作者Qv, Dehu
作者单位兰州理工大学土木工程学院
第一作者单位土木工程学院
通讯作者单位土木工程学院
第一作者的第一单位土木工程学院
推荐引用方式
GB/T 7714
Qv, Dehu. The difference between vapor injection cycle with flash tank and intermediate heat exchanger for air source heat pump: An experimental and theoretical study[J]. Energy,2021,221(/).
APA Qv, Dehu.(2021).The difference between vapor injection cycle with flash tank and intermediate heat exchanger for air source heat pump: An experimental and theoretical study.Energy,221(/).
MLA Qv, Dehu."The difference between vapor injection cycle with flash tank and intermediate heat exchanger for air source heat pump: An experimental and theoretical study".Energy 221./(2021).
条目包含的文件 下载所有文件
文件名称/大小 文献类型 版本类型 开放类型 使用许可
The difference betwe(5695KB)期刊论文作者接受稿开放获取CC BY-NC-SA浏览 下载
个性服务
查看访问统计
谷歌学术
谷歌学术中相似的文章
[Qv, Dehu]的文章
百度学术
百度学术中相似的文章
[Qv, Dehu]的文章
必应学术
必应学术中相似的文章
[Qv, Dehu]的文章
相关权益政策
暂无数据
收藏/分享
文件名: The difference between vapor injection cycle with.pdf
格式: Adobe PDF
所有评论 (0)
暂无评论
 

除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。